Please use this identifier to cite or link to this item: https://dspace.iiti.ac.in/handle/123456789/5748
Title: A Two-Level Hierarchical Controller to Enhance Stability and Dynamic Performance of Islanded Inverter-Based Microgrids With Static and Dynamic Loads
Authors: Raju, E. S.N.P.
Jain, Trapti
Keywords: Control system analysis;Control system stability;Control systems;Decentralized control;Distributed power generation;Dynamic loads;Eigenvalues and eigenfunctions;Electric inverters;Hierarchical systems;Integrated control;MATLAB;MIMO systems;Phase measurement;Phasor measurement units;Reactive power;Time domain analysis;Voltage control;Hierarchical controllers;Inverter interfaced distributed generations;Islanded microgrid;Model order reduction;Phasor Measurement Unit (PMUs);Power system dynamics;Power system stability;Stability analysis;Controllers
Issue Date: 2019
Publisher: IEEE Computer Society
Citation: Raju, E. S. N. P., & Jain, T. (2019). A two-level hierarchical controller to enhance stability and dynamic performance of islanded inverter-based microgrids with static and dynamic loads. IEEE Transactions on Industrial Informatics, 15(5), 2786-2797. doi:10.1109/TII.2018.2869983
Abstract: This paper proposes phasor measurement unit (PMU) supported two-level hierarchical controller to enhance stability and dynamic performance of islanded inverter-based microgrids with static and dynamic loads. The proposed hierarchical controller consists of a local decentralized controller for each inverter-interfaced distributed generation (IIDG) unit at the primary level helped by a multi-input multioutput centralized controller at the secondary level. The primary-level decentralized controller incorporates the addition of auxiliary control terms to the conventional droop controller. The auxiliary control terms are based on the total real and reactive power generation information acquired from wide area measurement system through PMUs and the desired power sharing of each IIDG unit. The secondary-level centralized controller, on the other hand, enhances the performance of each local decentralized controller by compensating the voltage and frequency deviations caused by the load disturbances. The performance of the proposed hierarchical controller has been demonstrated through eigenvalue analysis and time-domain simulation results carried out in MATLAB/SIMULINK environment. Further, in order to have a fair comparison, the performance of the proposed hierarchical controller, based on modal-based extended linear quadratic Gaussian (LQG) approach, has been compared with that of hierarchical controller based on state-based extended LQG approach. Simulation results revealed the capability of the proposed hierarchical controller to mitigate the unstable oscillations as well as to settle quickly at different operating points under the application of small-signal disturbances. © 2005-2012 IEEE.
URI: https://doi.org/10.1109/TII.2018.2869983
https://dspace.iiti.ac.in/handle/123456789/5748
ISSN: 1551-3203
Type of Material: Journal Article
Appears in Collections:Department of Electrical Engineering

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetric Badge: